Plan Review Notes
Plan Review Notes For Permit 04030451
Permit Number 04030451
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030451
 ADD: 2810 S DIXIE
 CONT: ALEXANDER KING CONST
 TEL: (561)441-2388
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STRUCTURAL COMPONENTS- WOOD CONNECT
 ORS, CONCRETE ANCHORS
 ************IMPORTANT*****************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 MISSING FLORIDA APPROVAL ON VARIOUS
 PRODUCT REPORTS, WILL REQUIRE LOCAL
 APPROVAL, FORM ATTACHED.SEE RULE 9B-72.
  
 2) PLANS CALL FOR HUGHES ANCHORS. HUGHES
 WAS BOUGHT OUT IN 1999. THERE IS NO
 FLORIDA LISTING FOR HUGHES UNDER THE FL
 PRODUCT APPROVAL SYSTEM. SUBMIT ANOTHER
 MANUFACTORER.
  
 3) SHEET A-5 SECTION# 1, INDICATES THE
 USE OF 5/8" CDX PLYWOOD ON THE FRONT
 PORTICO WALL, "FIRE DISTRICT" DOESN'T
 ALLOW TYPE VI CONSTRUCTION(WOOD) ON
 EXTERIOR WALLS, (VERTICAL SURFACES).
 SEE F102.1.
  
 4) THE SAME DETAIL SHOWS A MOLD LOCATED
 AT THE TOP OF THE PARAPET, BUT NO
 MENTION OF WHAT TYPE OF MATERIALS THAT
 ARE TO BE USED? F102.7 ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT SHALL BE CONSTRUCTED OF APPROV-
 ED NONCOMBUSTIBLE MATERIAL OR FIRE
 ETARDANT TREATED WOOD.
  
 5) ROOFING: F102.4 ROOF COVERINGS IN THE
 FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF A CLASS A OR B ROOF
 COVERINS AS DEFINED IN 1505.
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE THE POSITIVE/ NEGATIVE PRESSURES
 AS TO TABLE 1606.2B INTERIOR AND END
 ZONES.
  
 7) 1606.1.5 MAIN WIND-FORCE RESISTNG
 SYSTEM, PROVIDE A ROOF FRAMING PLAN
 INDICATING THE VERTICAL, HORIZONTAL &
 GRAVITY LOADS TO BE RESISTED.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 8) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 9) PROVIDE A WINDOW AND DOOR BUCK DETAIL
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 10) PROVIDE THE MINIMUM DESIGN TYPE THIS
 BUILDING IS DESIGNED TO TYPE IV OR V?
 SEE TABLE 600 3'-10' REQUIRE:
 TYPE IV1HR
 TYPE V2HR
  
 11) 705.1.1.2. OPENINGS LESS THAN 15'-0"
 REQUIRE OPENING PROTECTIVES, PROVIDE
 45 MINUTE PROTECTIVES FOR REAR DOORS.
  
 12) 1503.4.1 GUTTERS AND LEADERS PLACED
 ON THE OUTSIDE OF BUILDINGS SHALL BE
 NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF
 SCHEDULE 40 PLASTIC PIPE.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.