| Plan Review Notes For Permit 04030414 |
| Permit Number |
04030414 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE WATTAGE OF THE | | | LUMINAIRES BEING ADDED (INDIVIDUALLY). | | | | | | 2} PLEASE SHOW ADDED LOADS, RECALCULATE | | | TO SHOW EXISTING AND ADDED LOAD TOTALS. | | | SEE 220.3(B)(4) FOR RECESSED LUMINAIRES. | | | | | | 3} PLEASE VERIFY WHETHER THE FIXTURES ON | | | CIRCUIT #34, SHEET E-01, ARE EXISTING, | | | OR BEING ADDED. | | | | | | 4} SEE PLUMBING REVIEW COMMENT REGARDING | | | ARCHITECTS SIGNATURE AND FIRM NUMBER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|