2004-04-13 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
 1. SHOW DESIGN PRESSURE FOR WINDOWS AND
 DOORS ON ELEVATIONS OF SHEET 1.
  
 2. THE ENGINEER SHALL INSPECT THE BUTT
 GLASS INSTALLATION AND SIGN & SEAL A
 LETTER STATING IT IS INSTALLED PER HIS
 SPECIFICATIONS BEFORE C/O OF HOUSE.
  
 3. SUBMIT MFGR'S SPECIFICATIONS FOR THE
 SEALANT TO BE USED IN THE BUTT GLASS TO
 GLASS INSTALLATION.
  
 4. A NOC MUST BE FILED AND A COPY
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 5. FEES HAVE BEEN ADJUSTED TO REFLECT
 CORRECTION OF SQ. FT. ON PLANS.
 ADDITIONAL FEES OF $10.50 TO BE PAID AT
 TIME OF PERMIT PICKUP.
  
  