2004-03-22 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 600.
  
 2.PLEASE INDICATE NEW OR EXISTING
 A/C EQUIPMENT.PROVIDE MODEL, BTU OF
 THE AHU & SEER OF THE CU.
  
 3.PROVIDE PLANS INDICATING DUCT/GRILLE
 SIZE, MATERIAL AND LAYOUT.
  
 PLEASE NOTE, RETURN AIR REQUIRED FROM
 BEDROOM AREAS PER REVISED 2001 FBC(M)
 EFFECTIVE JUNE 30, 2003.
  