Plan Review Notes
Plan Review Notes For Permit 04030345
Permit Number 04030345
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-27 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P1 SANITARY RISER ISOMETRIC,
 A CHECK VALVE AND GATE VALVE ARE REQUIR-
 ED WITH THE GATE VALVE ON THE DISCHARGE
 SIDE OF THE CHECK VALVE. SECTION 712.2
  
 REVIEW BY KEN STEVENS