 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 471.003(2)(H)2.A, FLORIDA STATE
 STATUTES, INSTALLATIONS MORE THAN 240
 VOLTS MUST BE ENGINEERED BY A
 "PROFESSIONAL ENGINEER".
  
 2} PLEASE INDICATE THE PRIMARY VOLTAGES,
 FEEDER SIZE AND OVERCURRENT PROTECTION
 FOR ALL TRANSFORMERS. PLEASE TAKE
 VOLTAGE DROP INTO CONSIDERATION.
  
 3} PLEASE INDICATE THE LOCATION OF THE
 OCP FOR EACH TRANSFORMER.
  