| 2004-04-13 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PLAN REVIEW NUMBER ON THE IMPACT |
| | FEE RECEIPT DOES NOT MATCH THE PLAN |
| | REVIEW NUMBER ON THE PLANS. PLEASE |
| | CORRECT. |
| | |
| | 3) THE TOTAL SQUARE FEET OF A/C AREA ON |
| | THE PLANS IS INCORRECT ON SHEET 3. IT |
| | SHOULD BE 3410 SQFT. |
| | |
| | 4) THE FL PRODUCT APPROVAL #S LISTED FOR |
| | TWO OF THE FIXED GLASS WINDOWS IN THE |
| | SCHEDULE ON SHEET 3 ARE INCORRECT. THEY |
| | SHOULD BE FL 243. |
| | |
| | 5) PLEASE CLARIFY THE TP4X CONNECTORS |
| | SPECIFIED ON SHEET 2 FOR THE 3-2X4 POSTS |
| | IN THE WALL BELOW THE GIRDER TRUSS. I |
| | COULD NOT LOCATE THEM IN THE CURRENT |
| | USP OR SIMPSON CATALOGES AND DID NOT SEE |
| | FL PROD.APP. FOR IT. |
| | |
| | 6) THE WINDOW IN BATH #3 WHICH IS WITHIN |
| | 3 FEET HORIZONTALLY OF THE TUB IS |
| | REQUIRED TO BE TEMPERED BY FBC 2405.2. |
| | |
| | 7) SPECIFY THE ATTIC LIVE LOAD ON THE |
| | PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 8) FOR CLARITY, PLEASE INDICATE WHICH |
| | CONNECTORS ARE FOR THE FLOOR TRUSSES ON |
| | THE TRUSS TIE DOWN LAYOUT ON SHEET 9. |
| | |
| | 9) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| | SINGLE OUTSWING EXTERIOR DOOR AT BATH #2 |
| | |
| | 10) SUBMIT STATE PRODUCT APPROVAL WITH |
| | APPROVED STATUS FOR THE COLLIER GARAGE |
| | DOOR. |
| | |
| | 11) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE 8'X7' GARAGE DOOR. THE |
| | DRAWINGS SUBMITTED FOR THE COLLIER |
| | GARAGE DOOR IS LIMITED TO A MINIMUM SIZE |
| | OF 10'X6'. |
| | |
| | 12) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| | LISTS A NUE-VUE NVSTA 48 CONNECTOR. THE |
| | STATE PRODUCT APPROVAL SUBMITTED LISTS A |
| | NVRT 48 OR NVSTA 22. PLEASE CLARIFY. |
| | |
| | 13) THE TRUSS CONNECTOR SCHEDULE LISTS A |
| | SIMPSON HUC 412 CONNECTOR WITH 1505# OF |
| | UPLIFT. THE STATE PRODUCT APPROVAL |
| | SUBMITTED IS FOR A HU 412 WITH 905# OF |
| | UPLIFT. PLEASE CLARIFY. |
| | |
| | 14) THE SUBMITTAL FOR THE BUTT GLASS |
| | WIDOW IS INCOMPLETE AND HAS ERRORS. THE |
| | THIRD PARTY QUAILTY ASSURANCE IS |
| | REQUIRED. THE DIMENSIONS OF THE PANELS |
| | NEEDS TO MATCH THE ARCHITECTURAL PLANS. |
| | THE LOT # ON SHEET 1 OF 2 IS INCORRECT. |
| | SPECIFY THE DESIGN PRESSURES. SUBMIT |
| | THE CALCULATIONS. SUBMIT THE SPECS. FOR |
| | THE GE 1200 SILICONE. |
| | |