| Plan Review Notes For Permit 04030148 |
| Permit Number |
04030148 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-12-09 00:00:00 | DENIED: | | | 1.ENERGY CALCULATIONS INDICATE 13 SEER | | | EQUIPMENT WHEREAS THE EQUIPMENT SCHEDULE | | | ON PLAN SHEET M-1 SHOWS ONLY A 12 SEER. | | | PLEASE CORRELATE PLANS WITH THE ENERGY | | | CALCS. | | | | | | 2.PLEASE NOTE THE EQUIPMENT SCHEDULE | | | THE SENSIBLE/LATENT BTU'S ARE SHOWN | | | UNDER THE WRONG EQUIPMENT.5 TON | | | INDICATES 13,800 SENS BTU'S & 5,000 | | | LATENT BTU'S. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|