| 2005-05-19 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1] SHOW THE METER LOCATION ON THE PLAN. |
| | |
| | 2} PANEL "A" MOVED FROM ORIGINAL |
| | LOCATION. IF THE FEED WAS CHANGED FROM |
| | OVERHEAD TO UNDERGROUND, INDICATE |
| | DISCONNECTING MEANS REQUIRED PER 230.70, |
| | CITY AMMENDMENTS. CALL ME WITH ANY |
| | QUESTIONS REGARDING THIS ISSUE. |
| | |
| | 3} THE A/C SYSTEM ON THE PANEL SCHEDULE |
| | AND IN THE LOAD CALCULATION DO NOT |
| | CORRELATE WITH THE ORIGINAL, UNREVISED, |
| | MECHANICAL DRAWINGS. PLEASE CORRELATE |
| | THE TWO PLANS TO INDICATE ACTUAL |
| | INSTALLATION. |
| | |
| | 4} THE OCP FOR CIRCUIT #30, BATH GFI, |
| | DOES NOT COMPLY WITH 210.52(C)(3), 20 |
| | AMP. |
| | |
| | 4} CIRCUIT #32, SAME COMMENT, ARTICLE |
| | 210.52(B)(1). PANEL "A". |
| | |
| | 5} SEVERAL RECEPTACLES THAT WERE ON THE |
| | REVIEWED PLANS HAVE BEEN REMOVED FROM |
| | THIS PLAN, AND THE ROOMS THIS OCCURRED |
| | IN DO NOT COMPLY WITH WITH 210.52. |
| | SEE THE PLANS REVIEWED THIS SUBMITTAL |
| | FOR REDLINED LOCATIONS. PLEASE CHECK FOR |
| | ACTUAL PLACEMENTS FOR "AS BUILTS". |
| | |
| | CALL WITH QUESTIONS REGARDING COMMENTS |
| | OR CODE REQUIREMENTS. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |