| 2004-03-19 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} BOTH PANELS ON THE RISER ARE |
| | DESIGNATED AS "A". |
| | |
| | 2} THE RISER DIAGRAM INDICATES #3/0 |
| | FEEDERS TO THE SUB PANEL, THE PANEL |
| | SCHEDULE INDICATES #3 FEEDERS, PLEASE |
| | CORRELATE. |
| | |
| | 3} INDICATE THE LOCATION OF THE SERVICE |
| | EQUIPMENT ON THE PLAN. |
| | |
| | 4} THE DISCONNECT LOCATION FOR THE |
| | CONDENSER UNITS ARE IN VIOLATION OF |
| | 110.26. |
| | |
| | 5} NOTE #9 REFERS TO ALL CONDUCTORS |
| | BEING A MINIMUM OF #12, THERE ARE #14'S |
| | ON THE PANEL SCHEDULE, PLEASE |
| | CORRRELATE. |
| | |
| | 6} A SMOKE DETECTOR NEEDS TO BE ADDED |
| | OUTSIDE THE GUEST BEDROOM PER |
| | 8-1.4.1.6.2(2), "IMMEDIATE VICINITY". |
| | |
| | 7} ONLY THE RECEPTACLES IN THE BEDROOMS |
| | ARE MARKED AS BEING ARC FAULT |
| | PROTECTED,NOTE THAT ALL OUTLETS MUST BE |
| | PER |
| | 210.12, LIGHTS, SMOKE DETECTORS, FANS. |
| | |
| | 8} A RECEPTACLE MUST BE ADDED ON THE |
| | KITCHEN COUNTER PER 210.52(C)(1). |
| | |
| | 9} A RECEPTACLE PER 210.52(A)(1) MUST |
| | BE ADDED IN THE BREAKFAST ROOM. |
| | |
| | 10} THERE ARE TWO BEDROOMS LABELED #3 ON |
| | SHEET E-1.(GUEST BEDROOM). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |