Plan Review Notes
Plan Review Notes For Permit 04030142
Permit Number 04030142
Review Stop P
Sequence Number 2
Notes
Date Text
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) LAUNDRY SINK IS NOT VENTED. SECTION
 902.1
 B) WASH MACHINE REQUIRES A STANDPIPE
 AND A CLEANOUT 4 FT ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 708.10 & 1002.1
 C) MASTER BATH TUB, SHOWER & BIDET ALL
 REQUIRE A TRAP. SECTION 1002.1
 D) SHOWER IN BATH #3 REQUIRES A TRAP.
 SECTION 1002.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]