| Date |
Text |
| 2004-04-13 00:00:00 | DENIED |
| | 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.BASED UPON SBCCI BUILDING VALUATION |
| | DATA, PROJECT VALUATION OF $250.000 IS |
| | TO LOW AND THE REVISED VALUATION IS |
| | $297,419.ADDITIONAL PERMIT FEES OF |
| | $478.93 ARE DUE. SEC. 104.6.5 WEST PALM |
| | BEACH AMMENDMENTS TO THE FBC. |
| | |
| | 4.WHAT ROOF TILE ARE YOU USING? |
| | SPANISH "S" IS ON PLANS AND 2 DIFFERENT |
| | PRODUCT APPROVALS ARE SUBMITTED. |
| | |
| | 5.PRODUCT APPROVAL FOR K.D. WINDOWS |
| | ARE NOT LISTED ON THE DCA PRODUCT |
| | APPROVAL SITE. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONAN PLEASE SEE THE STATE |
| | WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6.A SEPARATE ROOFING PERMIT IS |
| | REQUIRED.CONTRACTOR NOT SIGNED ON AT |
| | TIME OF APPLICATION. |
| | |
| | 7.PRODUCT APPROVALS FOR GLASS BLOCK |
| | NOT SUBMITTED WITH PLANS.SUBMIT TWO |
| | COPIES OF PRODUCT APPROVAL SHOWING |
| | 1 HR PROTECTION. |
| | |
| | 8.TOTAL GROSS AREA ON PLAN IS NOT |
| | CORRECT. |
| | |
| | 9.PAGE A-2 CHECK NOTES...DO YOU MEAN |
| | FBC AND NOT FBD?PLEASE CLARIFY. |
| | |
| | 10.GENERAL ARCH. NOTES #8 ALL WINDOWS |
| | ARE TO BE IMPACT RESISTANT.PLEASE |
| | REVISE.IMPACT PROTECT IS CALLED OUT IN |
| | OTHER LOCATIONS. |
| | |
| | ANY QUESTIONS CALL ME |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |