| Plan Review Notes For Permit 04030137 |
| Permit Number |
04030137 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-01-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA STATUTES | | | | | | A) FROM THE PREVIOUS REVIEW: | | | BATH #3 TUB IS NOT VENTED. 902.1 | | | BATH #2 SHOWER IS NOT VENTED. 902.1 | | | MASTER BATH SHOWER REQUIRES A TRAP. | | | 1002.1 | | | B) NEW SHEETS REQUIRED FOR P-1 AND P-2 | | | SHOWING ALL CHANGES. HAND DRAWN | | | CORRECTIONS ON THE PLANS ARE NOT | | | ACCEPTABLE. SECTION 104.2.1.3. | | | C) SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 552.80(2)(B) | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|