| Plan Review Notes For Permit 04030137 |
| Permit Number |
04030137 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-12-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. SECTION | | | 104.2.1. | | | A) WASH MACHINE IS NOT VENTED. SECTION | | | 901.2.1. | | | B)BATH #3 TUB IS NOT VENTED AND | | | REQUIRES A TRAP. SECTIONS 901.2.1 AND | | | 1002.1. | | | C) BATH #2 IS LABELED AS BATH #3 AND | | | THE TUB IS NOT VENTED AND REQUIRES A | | | TRAP. SECTIONS 901.2.1 AND 1002.1. | | | D) MASTER BATH BIDET NOT VENTED AND | | | REQUIRES A TRAP. SECTIONS 901.2.1 AND | | | 1002.1. | | | 2) SEE EXAMPLE OF A SANT. RISER DIAGRAM | | | THAT WILL MEET THE CODE REQUIREMENTS ON | | | ATTACHED SHEETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|