| Plan Review Notes For Permit 04030137 |
| Permit Number |
04030137 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-22 00:00:00 | DENIED: | | | 1.RETURN AIR NOT INDICATED FOR THE | | | DEN/STUDY AREA. | | | | | | 2.RETURN AIR FROM AHU-2; TWO BRANCH | | | LINES INDICATED FROM THE RETURN, BUT | | | SHOW A SUPPLY SYMBOL. | | | | | | 3.RETURN AIR IS INDICATED FROM THE | | | LINEN CLOSET.IS THIS CORRECT? | | | | | | 4.SEER INDICATED ON THE PLAN IS A 12 | | | SEER RATING.ACCORDING TO THE ENERGY | | | CALCULATIONS THE SEER SHALL BE A MINIMUM | | | OF 13 SEER. | | | | | | 5.NOTE 21 ON PLAN SHEET M-1 INDICATES | | | ONLY A 10.5 SEER MINIMUM.THE SEER CAN | | | NOT BE LESS THAN THE ENERGY CALCS | | | REQUIRE. | | | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|