Text |
| 2004-04-13 00:00:00 | DENIED |
| | 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSEAND A COPY SUBMITTED TO THIS |
| | OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3. BASED UPON SBCCI BUILDING VALUATION |
| | DATA, PROJECT EVALUATION OF $220,000 IS |
| | TO LOW AND THE REVISED VALUATION IS |
| | $297,419.ADDITIONAL PERMIT FEES OF |
| | $781.91 ARE DUE.104.6.5 WEST PALM |
| | BEACH AMMENDMENT TO THE FBC. |
| | |
| | 4.WHAT ROOF TILE ARE YOU USING? |
| | TWO DIFFERENT PRODUCT APPROVALS HAVE |
| | BEEN SUBMITTED. SPANISH "S" IS |
| | SPECIFIED ON PLAN. |
| | |
| | 5.PRODUCT APPROVAL FOR K.D> WINDOWS |
| | ARE NOT LISTED ON THE DCA PRODUCT |
| | APPROVAL SITE. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6.SEPERATE ROOFING PERMIT REQUIRED. |
| | CONTRACTOR NOT SIGNED ON AT TIME OF |
| | APPLICATION. |
| | |
| | 7.SURVEY AND SITE PLAN DON'T MATCH. |
| | |
| | 8.PRODUCT APPROVALS FOR GLASS BLOCK |
| | ARE MISSING. SUBMIT 2 COPIES. |
| | |
| | 9.TOTAL GROSS AREA LISTED ON PLAN IS |
| | NOT CORRECT. |
| | |
| | 10.PAGE A-2 CHECK NOTES TO YOU MEAN |
| | FBC, NOT FBD?CLARIFY |
| | |
| | 11.GEN ARCH. NOTES # 8 ALL WINDOWS |
| | ARE TO BE IMPACT RESISTANT. PLEASE |
| | CLARIFYSINCE IMPACT PROTECTION IS ALSO |
| | SPEC'D OUT IN OTHER LOCATIONS. |
| | |
| | 12.GARDEN COURT:TABLE 600 |
| | CALCULATIONS NOT ACCURATE. |
| | TOTAL AREA 318 SQ. FT. X 20% = 63SQ.FT. |
| | ALLOWABLE OPENINGS.ACTUAL OPENINGS |
| | ARE 91.25 SQ. FT..PLEASE CHANGE AREA |
| | TO COMPLY WITH TABLE 600 ALLOWABLE |
| | OPENINGS. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |