| Plan Review Notes For Permit 04030134 |
| Permit Number |
04030134 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-01 00:00:00 | DENIED: | | | 1.RETURN AIR REQUIRED FROM DEN/STUDY | | | AREA.2001 FBC(M) 601.4. | | | | | | 2.SUPPLY DUCT TO THE MASTER BATH AREA | | | (AHU#2) DOES NOT INDICATE SIZE. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PROVIDE INFORMATION/CALCULATION FOR | | | COMBUSTION AIR FOR THE GAS DRYER.2001 | | | FBC(M) CHAPTER 7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|