| Plan Review Notes For Permit 04030134 |
| Permit Number |
04030134 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-25 00:00:00 | 1) BOTH PANELS ARE LABELED A | | | | | | 2) RISER SHOWS 3/0 PANEL SCHEDULE SHOWS | | | #3 | | | | | | 3) SERVICE LOCATION NOT SHOWN | | | | | | 4) AC DISC. NOT TO 110.26 | | | | | | 5) NEED TO CHANGE NOTE #912 GA MIN? | | | | | | 6) OUTSIDE THE BEDROOM SD MISSING FOR | | | THE GUEST BDRM | | | | | | 7) ALL OUTLETS IN ROOM TO AFCI PROTECTED | | | FANS, SD LIGHTS ARE INCLUDED | | | | | | 8) AN OUTLET PER 210.52A1 MUST BE ADDED | | | IN BREAKFAST ROOM | | | | | | 9) TWO #3 BEDROOMS ON PLANS | | | | | | 10) NO OUTLET ON FRONT ODF HOUSE |
|