Plan Review Notes
Plan Review Notes For Permit 04030134
Permit Number 04030134
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-15 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.FBC 11-4.23.2 EXCEPTIONS
 ATLEAST ONE BATHROOM DOOR SHALL HAVE A
 29 INCH CLEAR OPENING.
  
 4.GENERAL ARCH. NOTES #8 ALL WINDOWS
 ARE TO BE IMPACT RESISTANT.THIS
 CONFLICTS WITH OTHER NOTES OF IMPACT
 PROTECTION REQUIRED.
  
 5.SUBMIT MANUFATURER SPECIFICATIONS
 FOR AND UL LISTING INFORMATION FOR GAS
 BBQ AND HOOD.
  
 6.SUBMIT PRODUCT APPROVALS FOR GLASS
 BLOCK.TWO COPIES.
  
 7.BUTT GLASS NOT USED.REMOVE
 PRODUCT APPROVAL FOR THIS APPLICATION.
  
 8.ROOFING CONTRACTOR NOT SIGNED ON AT
 TIME OF APPLICATION.SEPARATE ROOFING
 PERMIT IS REQUIRED.PLANS SPEC OUT
 SPANISH "S" TILE ROOF.TWO DIFFERENT
 PRODUCT APPROVALS ARE SUBMITTED.
 SUBMIT CORRECT APPROVAL WITH SEPARATE
 ROOFING PERMIT.
  
 9.BUILDING VALUATION IS TOO LOW BASED
 UPON SBCCI BUILDING VALUATION TABLES.
 VALUATION HAS BE REVISED TO $292,864.
 ADDITIONAL PERMIT FEES ARE DUE. SEE
 APPLICATION FOR FEE DETAIL.
  
 10.KD WINDOWS NOT LISTED ON THE
 DCA PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11.SHEET A-2 NOTED REFER TO FBD
 CODE SECTIONS. CODE SHOULD BE FBC -
 (FLORIDA BUILDING CODE).
  
 12.ENEGY CALCS SUBMITTED ARE FOR THE
 WRONG ADDRESS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved