Plan Review Notes
Plan Review Notes For Permit 04030130
Permit Number 04030130
Review Stop P
Sequence Number 2
Notes
Date Text
2004-04-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 - THE FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED FROM THE PREVIOUS REVIEW. ALL
 COMMENT NUMBERS SHALL REMAIN THE SAME TO
 AVOID CONFUSION.
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 THIS IS NOT SHOWN TO FBC-2001 SATISFACT-
 ION.
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) - NOT SHOWN
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - THE VACUUM LINE IS NOT TO BE
 CONSIDERED AS A SUCTION INLET FOR THE
 SECTION REFERED TO ABOVE. SEE OFFICIAL
 INTERPRETATION SUBMITTED BY B.O.A.F.
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. - MINIMUM MEASUREMENT NOT
 SHOWN
 ***********NEW COMMENT*******
 1B FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2B INFORMATIONAL - TYP. SPAS FOR VINYL
 POOLS DETAIL UNCLEAR. THIS DETAIL SHALL
 BE CORRECTED IF SPA IS PART OF FUTURE
 INSTALLATIONS.
 3B) THERE IS A THIRD LINE CONNECTED TO
 THE POOL RETURN LINE THAT TERMINATES IN
 THE POOL. IS THIS A THIRD POOL RETURN?
 GENERAL SPECIFICATION INDICATE ONLY TWO
 POOL RETURN LINES PLEASE CLARIFY.
  