Plan Review Notes
Plan Review Notes For Permit 04030129
Permit Number 04030129
Review Stop P
Sequence Number 4
Notes
Date Text
2004-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) PLANS HAVE CHANGED SINCE THEY WERE
 PASSED BY PLUMBING REVIEW. NOW COMMENTS
 FROM PREVIOUS REVIEW AND NEW COMMENTS
 ARE NOW TO BE ADDRESSED.
 1) SKIMMER LINE AND VACUUM LINES ARE NOT
 LABELED CORRECTLY. PLEASE CORRELATE IN-
 FORMATION ON PLANS. SECTION 104.2.1
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)- NOW ONLY ONE SKIMMER SHOWN
 ON PLANS.
 3) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 4) THERE IS A THIRD LINE CONNECTED TO
 THE POOL RETURN LINE THAT TERMINATES IN
 THE POOL. IS THIS A THIRD POOL RETURN?
 GENERAL SPECIFICATION INDICATE ONLY TWO
 POOL RETURN LINES. PLEASE CLARIFY. SECT-
 ION 104.2.1
 5) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE COPIES OF SPECIFICATIONS, &
 DRAWINGS DRAWN TO SCALE WITH SUFFICIENT
 CLARITY AND DETAIL TO INDICATE THE NAT-
 URE AND CHARACTER OF THE WORK SHALL AC-
 COMPANY THE APPLICATION FOR A PERMIT. -
 SUBMIT 2 COMPLETE SETS OF PLANS FOR RE-
 VIEW. LOOSE SHEETS ARE NOT ACCEPTABLE.
 SURVEY SHEETS ARE NOT ATTACHED TO NEW
 SHEETS. SHEET 2 IS NOT CLEAR AND
 READABLE AND SHALL BE CHANGED. SUBMIT
 ONE SET OF OLD PLANS FOR COMPAIRISON.
 6) SHT 2 THE PIPING DIAGRAM SHALL REF-
 LECT THE PIPING INSTALLATION OF THE POOL
 DELETE REFERENCES TO THE FLOOR CLEANING
 HEADS, SPA MAIN DRAINS, THERAPY JETS, &
 TELESCOPING FOUNTAIN. ADD SECOND SKIMMER
 7) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE. 61G1-16.003
 8) SEE 61G1-16.004 FOR INFORMATION REQ-
 UIRED ON TITLE BLOCK. FS 481.2055
 9) ALL PLANS SHALL BE SIGNED AND SEALED
 BY ARCHITECT OF RECORD.
 10) SEE ATTACHED SHEET - BACKFLOW SHALL
 BE INSTALLED AND INSPECTED PRIOR TO THE
 POOL PERMIT BEING ISSUED. CITY CODE
 2853-95.
  