| Date |
Text |
| 2004-04-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | - THE FOLLOWING COMMENTS HAVE NOT BEEN |
| | ADDRESSED FROM THE PREVIOUS REVIEW. ALL |
| | COMMENT NUMBERS SHALL REMAIN THE SAME TO |
| | AVOID CONFUSION. |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | THIS IS NOT SHOWN TO FBC-2001 SATISFACT- |
| | ION. |
| | 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) - NOT SHOWN |
| | 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL) - THE VACUUM LINE IS NOT TO BE |
| | CONSIDERED AS A SUCTION INLET FOR THE |
| | SECTION REFERED TO ABOVE. SEE OFFICIAL |
| | INTERPRETATION SUBMITTED BY B.O.A.F. |
| | 4) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. - MINIMUM MESUREMENT NOT |
| | SHOWN. |
| | *************NEW COMMENT*************** |
| | 1B FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 2B INFORMATIONAL - TYP. SPAS FOR VINYL |
| | POOLS DETAIL UNCLEAR. THIS DETAIL SHALL |
| | BE CORRECTED IF SPA IS PART OF FUTURE |
| | INSTALLATIONS. |
| | 3B THERE IS A THIRD LINE CONNECTED TO |
| | THE POOL RETURN LINE THAT TERMINATES IN |
| | THE POOL. IS THIS A THIRD POOL RETURN? |
| | GENERAL SPECIFICATION INDICATE ONLY TWO |
| | POOL RETURN LINES. PLEASE CLARIFY. |
| | |