| 2004-04-27 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE CORRELATE PLUMB/ BLDG | | | AND ELECTRICAL PLANS. SOME AREAS SHOW | | | HEATER N/A , ELECTRICAL WIRING DIAGRAM | | | SHOWS A HEATER.THE CONTRACT FROM CONT | | | MENTIONS A HEATER. PLUMB RISER DOES NOT | | | INDICATE A HEATER NOR DOES IT SHOW A | | | SECOND PUMP AS ON ELECTRICAL?? | | | | | | PLEASE CORRELATE ALL OF THE ABOVE. | | | | | | IF AN ELECTRICAL TYPE HEATER IS INSTALL- | | | ED. PLEASE SUBMIT SPECS FOR HEATER | | | SHOWING LISTING. | | | PLEASE SUBMIT LOAD CALCULATION OF EXIST- | | | ING SERVICE W/ ALL NEW LOADS ADDED. | | | PLEASE ALSO INDICATE SIZE IF SERVICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|