Plan Review Notes
Plan Review Notes For Permit 04030129
Permit Number 04030129
Review Stop P
Sequence Number 1
Notes
Date Text
2004-03-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 6) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7) POOL PIPING DIAGRAM SHALL REFLECT
 THE POOL LAYOUT AND SHOW PIPING AND
 EQUIPMENT THAT WILL BE INSTALLED AND
 PIPING AND EQUIPMENT NOT TO BE INSTALLED
 SHALL BE DELETED FROM DIAGRAM.
 8) THE PLANS THAT ARE SUBMITTED ARE UN-
 CLEAR AND HARD TO READ. IN SOME PLACES
 THEY ARE IMPOSSIBLE TO READ. PER SECTION
 104.2.1 AND 104.3.1.1 OF THE CODE, TWO
 OR MORE COPIES OF DRAWINGS WITH SUFFICI-
 ENT CLARITY AND DETAIL SHALL ACCOMPANY
 THE APPLICATION FOR A PERMIT.
  