Plan Review Notes
Plan Review Notes For Permit 04030117
Permit Number 04030117
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-15 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW.
 PLEASE SEE FAC 61G15-23.002 FOR ALL
 REQ'D INFORMATION ON TITLE BLOCK FOR
 ENGINEERING FIRM.
 PLEASE ALSO SEE FS 471.023 FOR CA# ALSO
 REQ'D.
  
 2)NOTE: PLEASE SEE THAT A WIRING DIAGRAM
 WAS NOT SUBMITTED TO CLEARLY SHOW ALL
 EQUIPMENT. NOTES ON SKE-204 AND LAYOUT
 TO CORRELATE.
 THERE ARE SOME CIRCILED NOTES, 10,20,21
 DO THESE PERTAIN TO THIS PLAN?
  
 PLEASE SEE FS 553.80(2)(B) FOR PLANS.
 THIS NOTE MUST BE GIVEN AS A NOTICE TO
 PROFESSIONAL ON SECOND REVIEW WITH ANY
 OF THE SAME COMMENTS AS FIRST REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]