2004-03-11 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION REQ'D ON TITLE
 BLOCK FOR ENGINEERING FIRM.
 CA# AS REQ'D UNDER FS 471.023
 PLEASE ALSO SEE THAT ENGINEERS SIGNATURE
 IS REQ'D UNDER FS 471.025. PER RULING
 FROM FBPE'S, INITIALS ARE NOT ACCEPTABLE
 AND NAME MUST BE "SIGNED" AS SHOWN ON
 LICENSE.
  
 2)NOTE: PLEASE SUBMIT A WIRING DIAGRAM
 FOR COMPLETE WIRING OF AND FOR EQUIPMENT
  
  
 3)NOTE: PLEASE SHOW/CLARIFY WHERE AND
 HOW NEW EQUIPMENT IS BEING FED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  