| Plan Review Notes For Permit 04030038 |
| Permit Number |
04030038 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-30 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE INFORMATION ON THE | | | BUILDING CONSTRUCTION TYPE. | | | | | | 2.INDICATE OCCUPANCY TYPE. | | | | | | 3.PLAN SHEET S-5 INDICATES A WOOD | | | FLOOR/CEILING ASSEMBLY.DOES THIS HAVE | | | A FIRE RATING?IF SO, PLEASE INDICATE | | | UL LISTING FOR PENETRATIONS THROUGH | | | FIRE RATED ASSEMBLY. | | | | | | 4.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 402.2 OR 403.3. | | | | | | 5.PLAN SHEET M-3 CONDENSING UNIT | | | MOUNTING DETAIL, DETAIL INDICATES COPPER | | | TUBING/PIPE.PER 2001 FBC CHAPTER 13 | | | SUB-CHAPTER 611.1.ABC.1, ALL REFRIGERANT | | | PIPING SHALL BE INSULATED IN ACCORDANCE | | | WITH TABLE 6-11. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|