| Plan Review Notes For Permit 04030032 |
| Permit Number |
04030032 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-11 00:00:00 | DENIED:2ND REVIEW | | | REFERENCE REVIEW DATED 3-29-04 | | | COMMENT #1, REQUEST FOR BUILDING | | | CONSTRUCTION TYPE.PLAN SHEET M-3 | | | REVISION NOTE INDICATES THE BUILDING | | | TYPE WAS IDENTIFIED ON PLAN SHEET A-5. | | | A-5 DOES NOT INDICATE BUILDING | | | CONSTRUCITON TYPE. | | | | | | COMMENT #3, REQUEST FOR UL LISTING FOR | | | THE WOOD FLOOR/CEILING ASSEMBLY WAS NOT | | | ADDRESSED. | | | | | | COMMENT #4, OUTSIDE AIR CALCULATIONS | | | WERE PROVIDED BUT THE FLOOR PLAN DOES | | | NOT INDICATE OUTSIDE AIR INTAKE, LAYOUT | | | OR DUCT SIZE AND MATERIAL. | | | | | | NEW COMMENT - PLAN SHEET M-3 DETAIL OF | | | THE AIR HANDLING UNIT MOUNTING.DETAIL | | | INDICATES 4" DRYER DUCT TERMINATING | | | UNDER THE RETURN AIR PLENUM.SHOULD | | | THIS READ OUTSIDE AIR PLENUM?PLEASE | | | CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|