| Plan Review Notes For Permit 04030025 |
| Permit Number |
04030025 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHTS A-3 & A-4 SHOW LOCATION OF WASH | | | MACHINE ON FLOOR PLAN EACH TYPE UNIT. | | | SECTION 104.2.1. | | | 2) SHTS P-2 & P-4 (SANT. RISER) BIDET | | | NOT VENTED. SECTION 901.2.1. | | | 3) SHT P-2 LAV IN MASTER BATH LABLED W/C | | | AND 2ND LAV PIPING NOT SHOWN ON FLOOR | | | PLAN FOR UNITS A & B. SECTION 104.2.1. | | | 4) SHTS P-4 & P-5 CLEANOUT FOR WASH | | | MACHINE SHALL BE 4' AFF FOR ACCESS. | | | SECTION 708.10. | | | 5) SHT P-5 DOMESTIC WATER ISOMETRIC, AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | ISOMETRIC. WATER HAMMER ARRESTORS SHALL | | | BE LOCATED AT THE REFRIG. AND DISH WASH- | | | ER PER 604.9. ALL WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | | SOME ARE SHOWN. WH-PDI 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|