| Date |
Text |
| 2004-03-09 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON PROPER |
| | ELEVATION. |
| | |
| | 2) IS THE EXISTING APPROVED UNITS |
| | UNDER THE SAME OWNERSHIP AS THE NEW |
| | PROPOSED BUILDING. |
| | |
| | 3) THE ELECTRICAL LEGEND DOES NOT |
| | IDENTIFY REQUIRED ELECTRIC POWERED |
| | SMOKE DETECTORS. ONLY DUCT SMOKE |
| | DETECTORS SHOWN ON LEGEND. |
| | |
| | 4) THE WINDOW SCHEDULE SHALL IDENTIFY |
| | ALL EGRESS WINDOWS IN THE REMARKS |
| | SECTION. |
| | |
| | 5) PLANS DO NOT INDICATE INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS. |
| | |
| | 6) PLANS DO NOT INDICATE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR METAL |
| | STAIR RAILINGS. |
| | |
| | 7) ALL EGRESS WINDOWS SHALL BE NOTED |
| | ON THE ARCHITECTURAL PLANS. |
| | |
| | 8) PLEASE SHOW ALL TENANT DEMISING |
| | WALLS WITH HOURLY RATINGS WITH UL |
| | NUMBERS. |
| | |
| | 9) NO MENTION OF FIRE EXTINGUISHERS. |
| | |
| | 10) PLEASE INDICATE CONSTRUCTION TYPE |
| | ON PLANS, AND OCCUPANT LOADS. |
| | |
| | 11) PLEASE PROVIDE A LIFE SAFETY PLAN. |
| | |
| | 12) THE FIRE HYDRANT SHOWN ON C-5 SHALL |
| | HAVE 7 1/2 FEET CLEARANCE TO THE FRONT |
| | AND SIDES AND 4 FEET TO THE REAR. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |