| Date |
Text |
| 2004-05-20 00:00:00 | ************ UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | MISSING IN ONE BEDRM |
| | |
| | 4 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | MISSING REAR. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PANEL SCHEDULE SHOWS RECEPTS ONLY. |
| | 2002 NEC 210.12 |
| | |
| | 7)NOTE: PLEASE SEE OCP SHOWN FOR 10KW |
| | HEAT IS AT 50A. PLEASE SEE 424.3B FOR |
| | MIN 125%. |
| | |
| | 8)NOTE: PLEASE SEE PANEL SCHEDULE DOES |
| | NOT INCLUDE THE TWO MIN REQ'D SMALL |
| | APPLIANCE CIRCUITS. 210.11/ |
| | |
| | 9)NOTE: PLEASE LOAD CALCULATIONS, LOAD |
| | FOR AHU MAY NOT BE DERATED AT 40%. |
| | PLEASE SEE 220.32 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |