2004-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021437
 ADD: 515 N FLAGLER DR # ____
 CONT: HOLT LEE
 TEL: (954)725-4881
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ADDRESS WITH SUITE ON APPLICATION.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4)11-4.1.3(11) PRIVATE TOILET ROOMS IN
 PRIVATE OFFICES SHALL BE ADAPTABLE,
 BACKING IN WALLS, WITH THE REQUIRED
 5'-0" TURNING CIRCLE.
  
 5)609.2.1 TYPE II BUILDING, 609.2.1
 ALL BACKING IN WALLS TO BE "FIRE RETARD-
 ANT TREATED WOOD".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026