| Plan Review Notes For Permit 04021437 |
| Permit Number |
04021437 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04021437 | | | ADD: 515 N FLAGLER DR # ____ | | | CONT: HOLT LEE | | | TEL: (954)725-4881 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) ADDRESS WITH SUITE ON APPLICATION. | | | | | | 2) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 4)11-4.1.3(11) PRIVATE TOILET ROOMS IN | | | PRIVATE OFFICES SHALL BE ADAPTABLE, | | | BACKING IN WALLS, WITH THE REQUIRED | | | 5'-0" TURNING CIRCLE. | | | | | | 5)609.2.1 TYPE II BUILDING, 609.2.1 | | | ALL BACKING IN WALLS TO BE "FIRE RETARD- | | | ANT TREATED WOOD". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|