| 2004-04-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) FROM PREVIOUS REVIEW: SEAL IMPRESSION |
| | NOT CLEAR ENOUGH TO READ INFORMATION RE- |
| | QUIRED BY FAC 61G15-23.001. |
| | 2) FROM PREVIOUS REVIEW: |
| | A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025- PER FBPE INITIALS ARE NOT |
| | ACCEPTABLE. SIGNATURE REQUIRED ON SEALS. |
| | FS 471.025 |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 - THE NAME |
| | OF THE ENGINEERING BUSINESS HAS BEEN |
| | DELETED FROM THE TITLE BLOCK. |
| | 3) FROM PREVIOUS REVIEW: SHOW CLEAR |
| | FLOOR SPACE FOR BREAK ROOM SINK PER |
| | SECTION 11-4.24.5 - PLEASE SHOW ON PLANS |
| | 4) FROM PREVIOUS REVIEW: SHT P-2.1 DE- |
| | TAIL #5 SANITARY RISER DIAGRAM, EVERY |
| | DRY VENT SHALL RISE VERTICALLY TO A MIN- |
| | IMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF |
| | THE HIGHEST TRAP OR TRAPPED FIXTURE BE- |
| | ING VENTED. SECTION 905.4 - RESPONSE |
| | NOTED, BUT THE VENTS FOR FLOOR DRAINS |
| | ARE TURNING HORIZONTAL BELOW THE FLOOD |
| | LEVEL RIM. SEE SHEET P-3.1 |
| | |
| | REVIEW BY KEN STEVENS |