Plan Review Notes
Plan Review Notes For Permit 04021431
Permit Number 04021431
Review Stop P
Sequence Number 2
Notes
Date Text
2004-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SEAL IMPRESSION
 NOT CLEAR ENOUGH TO READ INFORMATION RE-
 QUIRED BY FAC 61G15-23.001.
 2) FROM PREVIOUS REVIEW:
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025- PER FBPE INITIALS ARE NOT
 ACCEPTABLE. SIGNATURE REQUIRED ON SEALS.
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - THE NAME
 OF THE ENGINEERING BUSINESS HAS BEEN
 DELETED FROM THE TITLE BLOCK.
 3) FROM PREVIOUS REVIEW: SHOW CLEAR
 FLOOR SPACE FOR BREAK ROOM SINK PER
 SECTION 11-4.24.5 - PLEASE SHOW ON PLANS
 4) FROM PREVIOUS REVIEW: SHT P-2.1 DE-
 TAIL #5 SANITARY RISER DIAGRAM, EVERY
 DRY VENT SHALL RISE VERTICALLY TO A MIN-
 IMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF
 THE HIGHEST TRAP OR TRAPPED FIXTURE BE-
 ING VENTED. SECTION 905.4 - RESPONSE
 NOTED, BUT THE VENTS FOR FLOOR DRAINS
 ARE TURNING HORIZONTAL BELOW THE FLOOD
 LEVEL RIM. SEE SHEET P-3.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]