Plan Review Notes For Permit 04021431
Permit Number 04021431
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-20 00:00:00************ UNSAT*************
  
 1 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE NEC, RECEPTS 180VA PER RECEPT
 SHOWS 4VA PER SQ FT.
 PLEASE ALSO SEE A/C LOAD ?
  
 2)NOTE: PLEASE SEE FS 471.025, PLEASE
 HAVE ENGINEER SIGN, DATED AND SEAL PLANS
 AS REQ'D. MUST BE SIGNED WITH A COMPLETE
 SIGNATURE CONTAINING A MIN OF FIRST
 AND LAST NAME AS SHOWN ON LICENSE/SEAL
 PER FBPE'S. INITIALS ARE NOT ACCEPTABLE
 PER FBPE'S.
  
 PLEASE ALSO NOTE, ARCHITECT HAS LICENSE
 # LISTED ON TITLE BLOCK AS CERTIFICATE
 OF AUTH #. PER DPBR, THIS IS THE ARCH
 LICENSE AR#. ARCH MAY NOT HAVE AIA,
 IN TITLE BLOCK PER FS 481.219.IS
 THE ABOVE IS FOR ALL SHEETS AND TRADES
 WEATHER OR NOT COMMENT IS MADE BY
 REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717