Plan Review Notes
Plan Review Notes For Permit 04021431
Permit Number 04021431
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-05 00:00:00**************UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS ARE REQ'D TO
 BE SIGNED, DATED AND SEALED UNDER FS
 471.025
 PLANS REQUUIRED TO HAVE AN ORIGINAL
 SIGNATURE, A "STAMPED" SIGNATURE IS NOT
 PERMITTED.
 PLEASE ALSO SEE A RUBBER/STAMPED SEAL
 IS ALSO NOT PERMITTED, SHALL BE A METAL
 TYPE IMPRESSION SEAL.
 FAC 61G15-23.001
  
 2)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQUIRED UNDER
 FS 471.023 FOR ENGINEERSFS 481.219
 FOR ARCHS.
 INFORMATION REQUIRED PER FAC 61G15-23.
 - .002.
 CERTIFICATE IF AUTHORIZATION # IS REQ'D.
 PLEASE SEE 61G1-16.004 FOR ARCH'S
 REQUIREMENTS.
  
 THE ABOVE TWO COMMENTS IS REQUIRED FOR
 ALL PLANS, SHEETS AND FOR ALL TRADES
 WEATHER OR NOT COMMENT IS MADE BY ANY
 OTHER REVIEWER.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLANS SHOW A NEW PANEL FOR NEW
 SPACE. WHERE IS PANEL FED FROM, FEEDERS
 OCP, LOAD ON EXISTING? ETC.215.5
  
 5)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 6)NOTE: PLEASE CLARIFY LOCATION OF PANEL
 IN "FILE STORAGE AREA". PLEASE SEE
 110.26, 408.7 ETC.
  
 7)NOTE: PLEASE CLARFIY REQUIRED SIGN
 CIRCUIT PER 600.5
  
 8)NOTE: PLEASE ALSO SEE 210.62 FOR
 WINDOW RECEPTS REQUIRED.
  
 9)NOTE: PLEASE CLARIFY NO LOADS SHOWN
 FOR 3 A/C UNITS, YET OCP IS SHOWN MUCH
 HIGHER THAN AHU.??
 PLEASE CORRELATE WITH MECHANICAL PLANS
 PLEASE ALSO SEE 210.63 FOR RECEPT REQ'D
 FOR A/C EQUIPMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved