| 2004-04-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE DEMOLITION PLAN NOTES REFER TO | | | NOTES SHEET ID-01, PLEASE PRONIDE THAT | | | SHEET IF APPLICABLE, IF NOT REMOVE NOTE | | | FROM PLAN. | | | | | | 2} PLEASE INDICATE THE LOCATION OF THE | | | "EXISTING ELECTRICAL PANEL". | | | | | | 3} VERIFY AND NOTE ON PLAN THAT NO OTHER | | | CIRCUITS FROM PANELS OUTSIDE THE AREA | | | OF WORK RUN THROUGH THIS SPACE. IF SO | | | INDICATE LOCATION AND PANEL LOCATION | | | AND DESIGNATION. | | | | | | 4} THE ENGINEER OF RECORD NEEDS TO DATE | | | HIS SEAL PER 61G15-23.002 FAC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|