| 2004-04-17 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | MASTER BEDRM. |
| | |
| | 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52EREAR) |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPT ALONG |
| | KITCHEN COUNTERSPACE PER 210.52C1 |
| | |
| | 5)NOTE: PLEASE LIST REQ'D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE |
| | PER 210.12 2002 NEC. |
| | |
| | 6)NOTE: PLEASE SEE SD NEXT TO BATH, |
| | PLEASE SEE NFPA-72 8-1.4.2 MUST BE A |
| | MIN OF 3' FROM BATH. |
| | |
| | 7)NOTE: PLEASE SEE GARAGE DR OPENER IS |
| | SHOWN AS 220V?? PLEASE VERIFY. |
| | |
| | 8)NOTE: PLEASE SEE RISER, SHOWS PANEL |
| | BACK TO BACK W/ METER. |
| | PLEASE SEE 230.70 LOCAL AMENDMENTS, |
| | IF MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| | -S INSIDE BDLG W/OUT OCP, A MAIN IS |
| | REQ'D ON OUTSIDE OF BLDG W/ OCP. |
| | PANEL IS SHOWN ON PLANS ON THE OTHER |
| | SIDE OF GARAGE.?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |