2004-04-17 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 MASTER BEDRM.
  
 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR)
  
 4)NOTE: PLEASE SEE MISSING RECEPT ALONG
 KITCHEN COUNTERSPACE PER 210.52C1
  
 5)NOTE: PLEASE LIST REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210.12 2002 NEC.
  
 6)NOTE: PLEASE SEE SD NEXT TO BATH,
 PLEASE SEE NFPA-72 8-1.4.2 MUST BE A
 MIN OF 3' FROM BATH.
  
 7)NOTE: PLEASE SEE GARAGE DR OPENER IS
 SHOWN AS 220V?? PLEASE VERIFY.
  
 8)NOTE: PLEASE SEE RISER, SHOWS PANEL
 BACK TO BACK W/ METER.
 PLEASE SEE 230.70 LOCAL AMENDMENTS,
 IF MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S INSIDE BDLG W/OUT OCP, A MAIN IS
 REQ'D ON OUTSIDE OF BLDG W/ OCP.
 PANEL IS SHOWN ON PLANS ON THE OTHER
 SIDE OF GARAGE.??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  