| Plan Review Notes For Permit 04021411 |
| Permit Number |
04021411 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-02 00:00:00 | 1) DEMOLITION, RENOVATION, CONSTRUCTION | | | TO COMPLY WITH NFPA 241. | | | | | | 2) TEMPORARY DUST PARTITIONS SHALL BE | | | CONSTRUCTED OF FIRE RESISTANT MATERIALS. | | | NON FIRE RATED VISQUEEN SHALL NOT BE | | | USED. NFPA 101 CH. 18.7.9 & NFPA 241 | | | COMPLIANCE SUMMARY TO BE FOLLOWED. | | | | | | 3) PLEASE EXPLAIN CALL-OUTS "SECURITY | | | LOCKED DOORS-TIE INTO FIRE ALARM SYSTEM | | | ON PAGE A-1. | | | | | | 4) PLEASE PROVIDE FLAME SPREAD INFO | | | ON CCT CURTAINS. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|