2004-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021406
 ADD: 2201 45TH ST
 CONT: BOVIS LEND LEASE
 TEL: (561)704-1928
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A1.20 INDICATES THE DEMOLISHION
 OFA EXISTING FENCE AND AWNING ABOVE.
 THE VARIOUS SECTIONS OF THE NEW FOOTER
 SLAB AND 10'-0" X 1'-0" CMU WALL WITH
 2" OF EFIS. THERE IS NO INFORMATION
 ON THE SIZE OF FOOTER SIZE AND NUMBER
 OF REBAR NOR THE UPRIGHTS.
 THE PLANS ALSO DO NOT INDICATE THE
 DEPTH OF THE FOOTER NOR IS THERE INFOR-
 MATION THAT WIND AND MOMENT OF OVER
 TURNING WAS CONSIDERED, OR IF THE FRAME
 WORK FOR THE AWNING WILL TRANSFER THESE
 LOADS?
 THE THIRD ITEM MISSING IS TYPE OF
 CONCRETE AND STRENGHT FOR VARIOUS POURS.
 THE SLAB DOESN'T INDICATE IF WIRE-
 MESH OR FIBERMESH IS TO BE USED?
 SINCE THIS A EXTERIOR AREA AND PARTS
 OF THE FLOOR SLAB INDICATE A CHAIN LINK
 OPEN AIR ROOF AREA HOW WILL RAIN WATER
 BE REMOVED FROM SLAB.
 INDICATE THE TRANSITION FROM THE INTER
 IOR OF THE BUILDING TO DECK?
 INDICATE IF THIS IS A EGRESS DOOR FROM
 THE INTERIOR AND IF SO WILL THE GATE BE
 LOCKED.
 THE AWNING IF CANVAS TO BE UNDER A SEP
 ERATE PERMIT AND WILL HAVE TO BE FIRE
 RESISTANT MATERIALS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026