| 2004-03-26 00:00:00 | DENIED: | | | 1.PLEASE NOTE, DETAIL OF UL DESIGN | | | L528, IN THE UL DIRECTORY DOES NOT | | | INDICATE ANY PENETRATIONS THROUGH THIS | | | ASSEMBLY.PLESE PROVIDE UL LISTING | | | FOR THE PENETRATIONS THROUGH THE RATED | | | ASSEMBLY. | | | | | | 2.PLEASE CLARIFY RATING ON PLAN SHEET | | | A-10 DETAIL #4, THE 1HR RATING IS AT THE | | | PARTITION WALL TO THE UNDERSIDE OF THE | | | CEILING CORRECT?IF THIS IS CORRECT, | | | THE FIRE DAMPER INDICATED ON PLAN SHEET | | | M-1 IS NOT REQUIRED BECAUSE THE WALL OR | | | RATING DOES NOT CONTINUE ABOVE THE | | | CEILING. | | | | | | 3.CLARIFY O.A. DUCT, IT APPEARS TO BE | | | ABOVE THE CEILING AND DOES NOT PENETRATE | | | AT THE POINT OF ENTRY, FIRE DAMPER IS | | | NOT REQUIRED. | | | | | | 4.PER 2001 FBC 705.2.2 EXCEPTION #1, | | | A SHAFT ENCLOSURE IS NOT REQUIRED FOR | | | OPENINGS TOTALLY WITHIN A DWELLING UNIT | | | & CONNECTING FOUR STORIES OR LESS. | | | | | | 5.PLANS SHALL BE SIGNED BY THE | | | ENGINEER NOT STAMPED WITH THEIR | | | SIGNATURE PER FS 471.025. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|