2004-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-1 WATER RISER DIAGRAM UNCLEAR
 AND HARD TO READ. SOME INFORMATION IS
 NOT READABLE. SECTION 104.2.1
 2) SHT P-1 WHITE OUT IS USED ON SOME
 PLUMBING NOTES. THIS IS NOT APPROVED.
 NOTES SHALL BE DELETED. SEC 1104.2.1.3
 3) SHT P-2 WATER RISER DIAGRAM IS UN-
 CLEAR AND HARD TO READ, RISER DOES NOT
 REFLECT THE FLOOR PLAN. FIRST AND SECOND
 FLOOR BATHROOM ARE NOT SHOWN ON RISER
 DIAGRAM. SECTION 104.2.1
 4) CERTIFICATE OF AUTHORIZATION IS NOT
 IN TITLE BLOCK AS REQUIRED. SEE BELOW..
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  