| 2004-07-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT P-1 WATER RISER DIAGRAM UNCLEAR |
| | AND HARD TO READ. SOME INFORMATION IS |
| | NOT READABLE. SECTION 104.2.1 |
| | 2) SHT P-1 WHITE OUT IS USED ON SOME |
| | PLUMBING NOTES. THIS IS NOT APPROVED. |
| | NOTES SHALL BE DELETED. SEC 1104.2.1.3 |
| | 3) SHT P-2 WATER RISER DIAGRAM IS UN- |
| | CLEAR AND HARD TO READ, RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. FIRST AND SECOND |
| | FLOOR BATHROOM ARE NOT SHOWN ON RISER |
| | DIAGRAM. SECTION 104.2.1 |
| | 4) CERTIFICATE OF AUTHORIZATION IS NOT |
| | IN TITLE BLOCK AS REQUIRED. SEE BELOW.. |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |