| Plan Review Notes For Permit 04021378 |
| Permit Number |
04021378 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-16 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE DRAWING SHOWS 8 METERS AND A MAIN | | | DISCONNECT, THE RISER SHOWS 5 AND NO | | | MAIN. PLEASE CORRELATE. | | | | | | 2} THERE IS NO DISCONNECT SHOWN FOR THE | | | CONDENSER FOR UNIT 1424. | | | | | | 3} THE LOW VOLTAGE SYMBOLS IN THE LEGEND | | | DO NOT MATCH THE SYMBOLS ON THE | | | DRAWING. | | | | | | 4} A CERTIFICATE OF AUTHORIZATION NUMBER | | | IS REQUIRED IN THE ENGINEERS TITLE | | | BLOCK PER 61G15-23.002. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|