2004-03-26 00:00:00DENIED:
 1.PLEASE NOTE, DETAIL OF UL DESIGN
 L528, IN THE UL DIRECTORY DOES NOT
 INDICATE ANY PENETRATIONS THROUGH THIS
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR THE PENETRATIONS THROUGH THE RATED
 ASSEMBLY.
  
 2.PLEASE CLARIFY RATING ON PLAN SHEET
 A-10 DETAIL #4, THE 1HR RATING IS AT THE
 CEILING CORRECT?IF THIS CORRECT,
 THE FIRE DAMPER INDICATED ON PLAN SHEET
 M-1 IS NOT REQUIRED BECAUSE THE WALL OR
 RATING DOES NOT CONTINUE ABOVE THE
 CEILING.
  
 3.CLARIFY O.A. DUCT, IT APPEARS TO BE
 ABOVE THE CEILING AND DOES NOT PENETRATE
 AT THE POINT OF ENTRY, FIRE DAMPER IS
 NOT REQUIRED.
  
 4.PER 2001 FBC 705.2.2 EXCEPTION #1,
 A SHAFT ENCLOSURE IS NOT REQUIRED FOR
 OPENINGS TOTALLY WITHIN A DWELLING UNIT
 & CONNECTING FOUR STORIES OR LESS.
  
 5.PLANS SHALL BE SIGNED BY THE
 ENGINEER AND NOT STAMPED WITH THEIR
 SIGNATURE AND NOT STAMPED WITH THEIR
 SIGNATURE PER FS 471.025.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.