Plan Review Notes
Plan Review Notes For Permit 04021378
Permit Number 04021378
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-07 00:00:00PLAN REVIEW PERFORMED ON 3/4/04
  
 1) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS PLEASE ANNOTE PLANS.
  
 2) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE.
  
 4) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS. IF THE FRONT DOORS
 DO NOT FRONT A STREET, ADDRESSES WILL
 BE REQUIRED ON BOTH SIDES FOR FIRE,
 PARAMEDICAL AND POLICE.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 7) PLEASE EXPLAIN EXITING RATIONALE FROM
 INSIDE THE UNITS.
  
 8) EMERGENCY INSTRUCTIONS FOR THE
 RESIDENTS SHALL BE PROVIDED.
  
 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 10) SUITABLE ROADS ARE REQUIRED DURING
 CONSTRUCTION.
  
 11) PLEASE INDICATE IF GARAGE DOOR
 IS RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910