 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE SIZE OF THE EQUIPMENT
 GROUNDING CONDUCTOR WITH THE FEEDERS ON
 THE RISER DIAGRAM.
  
 2} THE RISER SHOWS A MAIN DISCONNECT
 ANDTHE DRAWING SHOWS METERS
 & DISCONNECT, PLEASE CORRELATE.
  
 3}THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 4} PLEASE LABLE THE ROOMS ON THE ELECTR-
 ICAL PLANS TO CORRESPOND TO THE ARCHITEC
 TURAL PLANS.
  
 5} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSE UNITS.
  
 6} THE PANEL SCHEDULE REFERS TO "LIVING/
 BREAKFAST" ROOM.THE "BREAKFAST" ROOM
 MUST COMPLY WITH 210.52(B),20 AMP CIRC.
  
 7} THE "NOOK" AND DINING ROOM MUST COMPL
 Y WITH 210.52(B).
  
 8} THE DINING ROOM IN "2203" NEEDS TWO R
 ECEPTACLES ADDED TO COMPLY WITH 210.52.A
  
 9} SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026