| 2004-04-05 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE SIZE OF THE EQUIPMENT |
| | GROUNDING CONDUCTOR WITH THE FEEDERS ON |
| | THE RISER DIAGRAM. |
| | |
| | 2} THE RISER SHOWS A MAIN DISCONNECT |
| | ANDTHE DRAWING SHOWS METERS |
| | & DISCONNECT, PLEASE CORRELATE. |
| | |
| | 3}THE LAUNDRY CIRCUIT CALCULATION MUST |
| | COMPLY WITH 220.116(B).(1500 VA). |
| | |
| | 4} PLEASE LABLE THE ROOMS ON THE ELECTR- |
| | ICAL PLANS TO CORRESPOND TO THE ARCHITEC |
| | TURAL PLANS. |
| | |
| | 5} PLEASE PROVIDE PLANS FOR ALL UNITS, |
| | INCLUDING REVERSE UNITS. |
| | |
| | 6} THE PANEL SCHEDULE REFERS TO "LIVING/ |
| | BREAKFAST" ROOM.THE "BREAKFAST" ROOM |
| | MUST COMPLY WITH 210.52(B),20 AMP CIRC. |
| | |
| | 7} THE "NOOK" AND DINING ROOM MUST COMPL |
| | Y WITH 210.52(B). |
| | |
| | 8} THE DINING ROOM IN "2203" NEEDS TWO R |
| | ECEPTACLES ADDED TO COMPLY WITH 210.52.A |
| | |
| | 9} SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 10} NOTE THAT THE SIGNATURE OF THE EN- |
| | GINEER IS REQUIRED ON HIS/HER SEAL PER |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE |
| | STAMPS ARE NOT ACCEPTABLE PER F.B.P.E. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |