Plan Review Notes
Plan Review Notes For Permit 04021378
Permit Number 04021378
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021378 (5 UNIT)
 ADD: 1710 MISSION COURT
 CONT: WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW/
 DID NOT COME IN UNDER PLAN CHECK!!!
 ACTION: DENIED
 NOTE:
 AS NOTED PREVIOUSLY, A SIGNED AND
 SEALED LETTER FROM THE ARCHITECT OF
 RECORD INDICATING THE PLANS SUBMITED ARE
 A OCCUPANCY TYPE: (R2). WITH THE PLANS
 AND SOILS REPORTS STATING TOWNHOUSE,
 TOWNHOMES OR ROWHOUSES, IT IS TO BE MADE
 CLEAR THAT ALL DOCUMENTS SUBMITED ARE IN
 EFFECT TO BE BUILT AS A (R2) FOR USE AS
 CONDOMINIUM.
  
 1) 105.3 CITY ADMINISTRATIVE CODE,
 RESIDENT INSPECTOR, TO BE REQUIRED.
 CONTACT HAROLD PISKURA @ 805-6711.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A SITE PLAN SHALL BE REQUIRED INDICATING
 ALL SITE AMENITIES WITH DIMENSIONS
 BETWEEN BUILDINGS INDICATING ASSUMED
 PROPERTY LINES. TO CALCULATE ALLOWABLE
 OPENINGS SEE TABLE 600. PLANS CAN ONT
 BE CHECKED FOR ALLOWABLE OPENING SIZES
 UNTIL A SITE PLAN WITH DIMENSIONS AND
 ASSUMED PROPERTY LINES BETWEEN BUILDINGS
 ARE PROVIDED.
  
 3) SOILS REPORT NOT ORIGINAL SIGNATURE!
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) PROVIDE NOC RECORDED WITH THE CLERK
 0F COURT BEFORE A PERMIT CAN BE ISSUED.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) PROVIDE A SITE PLAN FOR FAIR HOUSING,
 PROVIDE AN ACCESSIBLE ROUTE TO ALL COM-
 MON ELEMENTS, INCLUDING CLUBHOUSE, GAZE-
 BOES, DUMPSTERS, POOLS, PARKING, AND A
 PATH OF TRAVEL TO THE PUBLIC WAY.
  
 8) PLANS ARE INCORRECT IN THE HEIGHT
 OF THE BUILDING, SEE CHAPTER 2 DEFINI-
 TIONS FOR GRADE AND HEIGHT, BUILDING,
 CORRECT A-7 & A-8.SHEET A-8 CORRECT
 MEAN ROF HEIGHT STILL LOW.
  
 9) SEE S-5:
 A) CORRECT: DOOR & WINDOW PRESSURE
 SCHEDULE, WALL AREAS, INTERIOR ZONES
 SHOULD BE REPRESENTED BY ZONE(4), NOT
 ZONE (1) AND END ZONES SHOULD BE REPRE-
 SENTED BY ZONE (5) NOT ZONE (2).
 B) ROOF NAILING ZONES, ZONE (3) NOTE
 DIFFICULT TO UNDERSTAND, IT CAN BE PRE-
 CEVED THAT ZONE (3) MAY BE NAILED THE
 SAME AS ZONE 2 OR NAILED AS NOTE FOR
 ZONE (3).
 C) ROOF NAILING CHART IS ONLY GOOD TO
 35' ABOVE GRADE. THE TRUE HEIGHT OF THE
 BUILDING WILL BE > THAN 35', THE ENGIN-
 EER OF RECORD SHALL PROVIDE THE ADDITION
 AL INFORMATION FOR REQUIRED FOR THE
 NAILING REQUIREMENTS FOR THE EFFECTED
 ROOF NAILING ZONES.
  
 10) AMARR GARAGE DOORS DO NOT MEET THE
 NEGATIVE PRESSURES FOR A BUILDING > THAN
 35' TALL WITH A ADJUSTMENT COEFFICIENT
 OF 1.09.SEE 1606.2D/1606.2E.
  
 11) SHEET A-12 DETAIL# 2 IS MISSING THE
 FIRE STOP BETWEEN VERTICAL & HORIZONTAL
 AREAS 2ND TO 3RD FLOOR WALL SHEATHING
 MISSING AT THIRD FLOOR STUD WALL.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2ND REQUEST !!!!!FOR THE PRODUCT TESTING
 REPORTS FOR THE STRUCTURAL COMPONENTS-
 TRUSS ANCHORS, CONCRETE TO WOOD, AND
 WOOD TO WOOD.
  
 13) 2ND REQUEST !!! PROVIDE TRUSS ENGIN-
 EERING SHEETS WITH ALL LOADING CASES, VE
 RTICAL, HORIZONTAL & GRAVITY LOADS.
 PLANS DO NOT INDICATE THE LOADING, ONLY
 THE ALLOWABLE VALUE FOR ANCHORS.
  
 14) SHEET M-1, M-2:
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
  
 15)GARAGE TO LIVING QUARTERS, GARAGE
 DOOR IS NOT LISTED ON THE GARAGE
 SCHEDULE. A 3/4 HR RATING IS REQUIRED 41
 1.2.6., 705.1.3.5, DOOR SHALL BE EQUIPED
 WITH AN APPROVED CLOSER.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026