| 2004-07-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) COMMENTS FROM PREVIOUS REVIEWS HAVE |
| | NOT BEEN ADDRESSED PROPERLY. COMMENT |
| | NUMBER TO STAY THE SAME TO AVOID CONFUS- |
| | ION. |
| | 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS SHALL LEGIBLY INDICATE THEIR NAME |
| | AND LICENSE NUMBER, AS WELL AS, THE NAME |
| | ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON |
| | EACH SHEET. A TITLE BLOCK WILL SATISFY |
| | THIS REQUIREMENT. FAC 61G15-23.002(2) |
| | AND FS 471.025. |
| | ***************NEW COMMENTS************* |
| | 1C) SHT P-1 PLUMBING GENERAL NOTES #19 |
| | HAS BEEN DELETED WITH WHITE-OUT. THIS IS |
| | NOT APPROVED. PLEASE DELETE NOTE ON PLAN |
| | PROPERLY. SECTION 104.2.1.3 |
| | 2C) SHT P-1 PLUMBING GENERAL NOTES #16 |
| | WHITE OUT USED ON NOTE TO DELETE INFOR- |
| | MATION. THIS IS NOT APPROVED. 104.2.3 |
| | 3C) WATER RISER DIAGRAMS ARE UNCLEAR AND |
| | HARD TO READ. THE WATER RISER DIAGRAM ON |
| | SHT P-2 DOES NOT REFLECT THE FLOOR PLAN. |
| | THE BATHROOM ON THE FIRST FLOOR AND THE |
| | BATHROOM ON THE SECOND FLOOR SHOWN ON |
| | THE FLOOR PLAN ARE NOT SHOWN ON THE |
| | WATER RISER DIAGRAM. SEC. 104.2.1 |
| | 4C) SEE ATTACHED SHEET IN REFERENCE TO |
| | FS 553.80(2)(B). FOUR TIMES THE FEE FOR |
| | THE PLAN REVIEW PORTION OF THE PERMIT |
| | SHALL BE IMPOSED IF THE SAME COMMENTS |
| | ARE NOT ADDRESSED PER FLA. STATUTE. |
| | (ATTACHED TO PERMIT #02041350 ONLY) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |