| Date |
Text |
| 2004-07-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) COMMENT FROM PREVIOUS REVIEW HAS NOT |
| | BEEN ADDRESSED. COMMENT NUMBER FROM PRE- |
| | VIOUS REVIEW TO STAY THE SAME TO AVOID |
| | CONFUSION, |
| | 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | **************NEW COMMENTS************** |
| | 1C) SHT P-1 DOMESTIC WATER SUPPLY DETAIL |
| | SHOWS THE WATER SUPPLY UNDER THE SLAB & |
| | SHOWS AN ADAPTOR FROM PVC TO COPPER. |
| | SUBMIT A DETAIL SHOWING TYPE OF FITTING |
| | AND MANUF. SPECIFICATION SHOWING APPROV- |
| | AL FOR UNDER SLAB INSTALLATION FOR THE |
| | ADAPTOR. SECTION 104.2.1 |
| | 2C) SHP P-1 SHOWS MAIN SHUTOFF VALVE IN- |
| | SIDE THE GARAGE, BUT PLUMBING GENERAL |
| | NOTES #13 INDICATES THAT VALVE SHALL BE |
| | LOCATED OUTSIDE OF THE BUILDING. PLEASE |
| | CLARIFY AND CORRELATE PLANS AND NOTES. |
| | SECTION 104.2.1 |
| | 3C) SHT P-1 PLUMBING GENERAL NOTES #19 |
| | HAS BEEN DELETED WITH WHITE-OUT. THIS IS |
| | NOT APPROVED. PLEASE DELETE NOTE ON PLAN |
| | PROPERLY. SECTION 104.2.1.3 |
| | 4C) SEE ATTACHED SHEET IN REFERENCE TO |
| | FS 553.80(2)(B). FOUT TIMES THE FEE FOR |
| | THE PLAN REVIEW PORTION OF THE PERMIT |
| | SHALL BE IMPOSED IF THE SAME COMMENTS |
| | ARE NOT ADDRESSED PER FLA. STATUTE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |