| Plan Review Notes For Permit 04021372 |
| Permit Number |
04021372 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-20 00:00:00 | *************DENIED********************* | | | 1) ALL NEW STAIRS SHALL HAVE HANDRAILS | | | ON BOTH SIDES. | | | | | | 2) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS | | | NFPA 101 2000 EDITION. | | | | | | 3) PLEASE EXPLAIN EXITING RATIONALE | | | FROM INSIDE THE UNITS. | | | | | | 4) EMERGENCY INSTRUCTIONS FOR RESIDENTS | | | SHALL BE PROVIDED. | | | | | | 5) WET FIRE HYDRANTS SHALL BE REQUIRED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 6) SUITABLE AND ACCESSIBLE ROADS ARE | | | REQUIRED DURING CONSTRUCTION. | | | | | | THESE NOTES AND COMMENTS ARE ALSO FOR | | | PERMITS: 04021350, 04021376, 04021354 | | | 04021358, 04021356 | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|