Plan Review Notes
Plan Review Notes For Permit 04021372
Permit Number 04021372
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-07-20 00:00:00*************DENIED*********************
 1) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS
 NFPA 101 2000 EDITION.
  
 3) PLEASE EXPLAIN EXITING RATIONALE
 FROM INSIDE THE UNITS.
  
 4) EMERGENCY INSTRUCTIONS FOR RESIDENTS
 SHALL BE PROVIDED.
  
 5) WET FIRE HYDRANTS SHALL BE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 6) SUITABLE AND ACCESSIBLE ROADS ARE
 REQUIRED DURING CONSTRUCTION.
  
 THESE NOTES AND COMMENTS ARE ALSO FOR
 PERMITS: 04021350, 04021376, 04021354
 04021358, 04021356
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910