| 2004-07-23 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) NO REDLINE CHANGES INITIALED & DATED |
| | BY THE DESIGNER OF RECORD ARE ALLOWED ON |
| | MASTER PLAN. REVISE THE ORIGINAL |
| | DRAWINGS. |
| | |
| | 3) CITY AMENDMENTS TO FBC TABLE 2306.1 |
| | REQUIRES THE ROOF SHEATHING TO BE NAILED |
| | WITH 8D RING SHANK NAILS IN ZONE THREE |
| | FOR BUILDINGS WITH A MEAN ROOF HEIGHT |
| | OF 25'- 35'. REVISE SCHEDULE ON S4. |
| | |
| | 4) PROVIDE A SCHEDULE FOR THE CASTCRETE |
| | LINTELS THAT WILL BE USED ON THE PLANS. |
| | SPECIFY THE ALLOWABLE SAFE LOADS IN THE |
| | SCHEDULE. |
| | |
| | 5) PROVDE STRUCTURAL DETAILS FOR THE |
| | GABLE END ROOF FRAMING AND OVERHANG. |
| | THE PLANS AND TRUSS LAYOUT ARE NOT CLEAR |
| | IN THIS AREA. |
| | |
| | 6) SPECIFY THE GRAVITY LOAD CAPACITY FOR |
| | THE CCO SIMPSON COLUMN CAP ON THE PLANS. |
| | |
| | 7) SPECIFY THE FASTENERS AND EMBED DEPTH |
| | ON THE STEEL COLUMN BASE DETAIL ON S5. |
| | CLARIFY THE NOTE THAT STATES WHERE |
| | NORMAL EMBEDMENT IS NOT POSSIBLE. |
| | PROVIDE AN ALTERNATE INSTALLATION DETAIL |
| | SHOWING EACH OPTION. |
| | |
| | 8) SPECIFY THE TRUSS CONNECTORS FOR THE |
| | GR03 ROOF GIRDERS, WHICH ARE SHOWN ON |
| | THE TRUSS LAYOUT PARALLEL TO ONE HOUR |
| | TENANT SEPARATION WALL. |
| | |
| | 9) REVISE CONNECTORS SPECIFIED FOR THE |
| | THREE PLY GIRDERS (GR01) AND TWO PLY |
| | GIRDERS (GR02,GR04,GR05) FROM THE |
| | SIMPSON MGT (MARK D) WHICH IS FOR A ONE |
| | PLY TRUSS TO AN APPROPRIATE CONNECTOR. |
| | |
| | 10) REVISE THE UPLIFT VALUE OF THE HETAL |
| | 20 CONNECTOR TO THE VALUE THAT DOES NOT |
| | INCLUDE A ONE-THIRD INCREASE IN THE |
| | STEEL CALCULATIONS (1810#). SEE |
| | FBC 1609.4.3. AND 2004 SIMPSON CATALOG. |
| | |
| | 11) SUBMIT COVER SHEETS FOR STATE |
| | PRODUCT APPROVAL WITH FL NUMBERS FOR ALL |
| | PRODUCTS REQUIRED BY FAC RULE 9B-72. |
| | MAKE COPIES FOR ALL THREE SETS OF PLANS. |
| | |
| | 12) PRODUCT APPROVAL THAT WAS SUBMITTED |
| | FOR THE ENTRY DOOR IS FOR A NON-IMPACT |
| | RATED DOOR AND WILL REQUIRE IMPACT |
| | PROTECTION. |
| | |
| | 13) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | LISTING INFO. FOR THE ONE HOUR FIRE |
| | RATED GLASS BLOCK. |
| | |
| | 14) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE OVERHEAD GARAGE DOORS DO NOT MEET |
| | THE REQUIRED DESIGN PRESSURES LISTED IN |
| | THE SCHEDULE ON THE PLANS. SUBMIT INFO. |
| | FOR GARAGE DOORS WITH ADEQUATE DESIGN |
| | PRESSURES. |
| | |